Advanced 35kV Oil-Immersed On-Load Tap Changing Power Transformer for Stable Grid Performance
Product Parameter
|
Parameter |
Specification |
| Rated Capacity | 3150kVA – 31500kVA |
| High Voltage | 33kV |
| Low Voltage | 6.3kV / 6.6kV / 10.5kV / 11kV |
| Frequency | 50Hz |
| Tap Range | ±5% or ±2×2.5% |
| Connection Group | Yd11 / YNd11 |
| Cooling Method | ONAN / ONAF (optional) |
| Insulation Class | Class F / Class H |
| No-Load Loss | 2600W – 17400W |
| Load Loss (75℃) | 23500W – 110200W |
| Impedance Voltage | 7% – 10% |
| Regulation Method | On-load Tap Changer (OLTC) |
| Insulation Level | LI 75kV / AC 35kV |
Product Applications
Product Advantages




Key Benefits
The 35kV oil-immersed OLTC power transformer is a high-performance solution for medium-voltage distribution systems requiring continuous voltage regulation and reliable energy transmission. Its combination of on-load tap changing technology, large capacity range, and high efficiency makes it suitable for utility networks, industrial facilities, and renewable energy projects.
With excellent stability, strong overload capacity, and long service life, it ensures consistent power quality and supports the evolving demands of modern electrical infrastructure.

FAQ
1. What is the main advantage of OLTC in a 35kV transformer?
OLTC allows voltage adjustment while the transformer is operating, ensuring uninterrupted power supply and stable voltage output under changing load conditions.
2. Can this transformer operate in renewable energy plants?
Yes, it is widely used in wind and solar power systems where voltage fluctuations are frequent and real-time regulation is required.
3. What is the typical overload capability of this transformer?
It can typically handle short-term overloads up to 110%–120% of rated capacity, depending on operating conditions.
4. Is this transformer suitable for smart grid applications?
Yes, it is fully compatible with modern smart grid systems due to its automatic voltage regulation and stable performance characteristics.
5. What cooling systems are available?
It supports ONAN (Oil Natural Air Natural) as standard, with optional ONAF (Oil Natural Air Forced) for higher load conditions.